NHXMH-O/-J
● Kupferleiter blank, ein- oder mehrdrähtig
● Isolation thermoplastische Polymermischung
● Aderkennzeichnung gem. VDE 0293
● Verseilung Adern verseilt, Füllmantel
● Mantel halogenfreie thermoplastische Polymermischung
|
Rated voltage :
|
Uo/U 300/500V
|
|
Test voltage :
|
2000V
|
|
Insulation resistance :
|
(+20°C):≧20MΩx km
|
|
Bending radius: :
|
stationary : 4 x cable diameterØ
flexible : 50 x cable diameterØ |
|
Temperature range :
|
stationary : -40°C - 70°C
flexible : -5°C - 70°C |
|
Radiation resistance :
|
≤80×10cJ/kg
|
|
Flame retardant :
|
IEC 60332-1
|
Order Number |
Number of cores × Nominal cross-sectional area mm² |
Cable diameter ~mm |
Copper weight ~kg/km |
Cable weight ~kg/km |
145001 |
1x1,5 |
7,0 |
15,0 |
49,0 |
145002 |
2x1,5 |
8,9 |
29,0 |
110,0 |
145003 |
1x2,5 |
7,6 |
24,0 |
60,0 |
145004 |
2x2,5 |
10,0 |
48,0 |
136,0 |
145005 |
1x4 |
8,6 |
39,0 |
80,0 |
145006 |
2x4 |
11,4 |
77,0 |
202,0 |
145007 |
1x6 |
9,9 |
58,0 |
111,0 |
145008 |
1x10 |
11,2 |
96,0 |
160,0 |
145009 |
1x16 |
11,9 |
154,0 |
232,0 |
145010 |
3G1,5 |
9,4 |
43,0 |
130,0 |
145011 |
4G1,5 |
10,2 |
58,0 |
151,0 |
145012 |
5G1,5 |
10,8 |
72,0 |
177,0 |
145013 |
7G1,5 |
11,4 |
101,0 |
209,0 |
145014 |
3G2,5 |
10,4 |
72,0 |
163,0 |
145015 |
4G2,5 |
11,3 |
96,0 |
200,0 |
145016 |
5G2,5 |
11,9 |
120,0 |
238,0 |
145017 |
7G2,5 |
13,5 |
168,0 |
300,0 |
145018 |
3G4 |
11,8 |
115,0 |
235,0 |
145019 |
4G4 |
13,3 |
154,0 |
300,0 |
145020 |
5G4 |
14,8 |
192,0 |
345,0 |
145021 |
3G6 |
13,4 |
173,0 |
323,0 |
145022 |
4G6 |
14,8 |
230,0 |
400,0 |
145023 |
5G6 |
16,0 |
288,0 |
475,0 |
145024 |
3G10 |
16,0 |
288,0 |
485,0 |
145025 |
4G10 |
17,4 |
384,0 |
603,0 |
145026 |
5G10 |
18,9 |
480,0 |
720,0 |
145027 |
3G16 |
19,7 |
461,0 |
850,0 |
145028 |
4G16 |
21,6 |
615,0 |
940,0 |
145029 |
5G16 |
23,8 |
768,0 |
1142,0 |
145030 |
3G25 |
24,3 |
720,0 |
1152,0 |
145031 |
4G25 |
27,0 |
960,0 |
1432,0 |
145032 |
5G25 |
29,0 |
1200,0 |
1800,0 |
145033 |
3G35 |
27,2 |
1008,0 |
1503,0 |
145034 |
4G35 |
29,9 |
1344,0 |
1930,0 |
145035 |
5G35 |
32,7 |
1680,0 |
2490,0 |
Für feste Verlegung in trockenen und feuchten Räumen,sowie im Mauerwerk und im Beton, auf, in und unter Putz.
Die direkte Einbettung in Rüttel-, Schüttel- oder Stampf-beton ist nicht zulässig. Für die Erdverlegung ist dieseLeitung nicht zu verwenden. Auch verwendbar im Freien,sofern Schutz vor direkter Sonneneinstrahlung ewähr-leistet ist.